Building & Landlord Data for 140 Albion St, San Francisco, CA

High Risk Building

Apartments at 140 Albion St are more likely to have maintenance issues than 73% of SF rentals.

  • 52% chance of no maintenance issues next year
  • 48% chance of at least one code violation next year

Building Information

Total Apartments 6
Class Multi-Family Residential
Year Built None
Zoning Code RM2
Area 7038 sq ft
Stories 3
Tax Abatements 11
Owner Name Camp Albion Llc
Owner Since 04/25/96

Department of Building Inspection Violations (90 found)

Date Filed Date Abated Violation Description Status
04/15/09 06/05/09 Provide fire extinguishers type 2a 10bc or equivalent.(905, 1001(n)hc / 3.29 sffc) A minimum of one '2-a:10-b:c' extinguisher for each 3,000 square feet of floor area is required. travel distance shall not exceed 75 feet to the nearest extinguisher. all fire extinguishers are required to be recharged and serviced annually and date tag must be current and posted by a qualified professional vendor. check the pressure gauge periodically as occasionally the seal may leaks and the unit becomes ineffective. Not active
04/15/09 06/05/09 Provide battery operated smoke detector at top of each enclosed stairs (909, 911 hc) A battery operated smoke detector is required at the top of each enclosed stairs / penthouse area and every third floor from the top. test smoke detectors on a regular basis and replace all batteries annually to maintain a working and functional device. Not active
04/15/09 06/05/09 Provide 1/2" throw deadlatch or single cylinder 1" throw deadbolt locks for rear or secondary door (706 hc) At secondary back door - top unit. Not active
04/15/09 06/05/09 This notice includes violations for the areas noted. Routine safety inspection of public and common areas at 140 - 144 albion street / 12 - 16 camp street. chapters 1, 2, & 3 of the san francisco housing code require that the department of building inspection perform periodic health & safety inspections of residential property. this routine inspection was conducted to assure that all requirements have been met per attached routine inspection checklist. Not active
04/15/09 06/05/09 Repair or replace malfunctioning emergency exit lights in public hallways / stairs (504, 1001 hc) Have the emergency lights tested annually and replace any malfunctioning units or expired backup batteries as required. Not active
04/15/09 06/05/09 Provide battery operated smoke detector at top of each enclosed stairs (909, 911 hc) A battery operated smoke detector is required at the top of each enclosed stairs / penthouse area and every third floor from the top. test smoke detectors on a regular basis and replace all batteries annually to maintain a working and functional device. Not active
04/15/09 06/05/09 Provide 1/2" throw deadlatch or single cylinder 1" throw deadbolt locks for rear or secondary door (706 hc) At secondary back door - top unit. Not active
04/15/09 06/05/09 This notice includes violations for the areas noted. Routine safety inspection of public and common areas at 140 - 144 albion street / 12 - 16 camp street. chapters 1, 2, & 3 of the san francisco housing code require that the department of building inspection perform periodic health & safety inspections of residential property. this routine inspection was conducted to assure that all requirements have been met per attached routine inspection checklist. Not active
04/15/09 06/05/09 Repair or replace malfunctioning emergency exit lights in public hallways / stairs (504, 1001 hc) Have the emergency lights tested annually and replace any malfunctioning units or expired backup batteries as required. Not active
04/15/09 06/05/09 Provide fire extinguishers type 2a 10bc or equivalent.(905, 1001(n)hc / 3.29 sffc) A minimum of one '2-a:10-b:c' extinguisher for each 3,000 square feet of floor area is required. travel distance shall not exceed 75 feet to the nearest extinguisher. all fire extinguishers are required to be recharged and serviced annually and date tag must be current and posted by a qualified professional vendor. check the pressure gauge periodically as occasionally the seal may leaks and the unit becomes ineffective. Not active
04/15/09 06/05/09 Provide battery operated smoke detector at top of each enclosed stairs (909, 911 hc) A battery operated smoke detector is required at the top of each enclosed stairs / penthouse area and every third floor from the top. test smoke detectors on a regular basis and replace all batteries annually to maintain a working and functional device. Not active
04/15/09 06/05/09 Provide 1/2" throw deadlatch or single cylinder 1" throw deadbolt locks for rear or secondary door (706 hc) At secondary back door - top unit. Not active
04/15/09 06/05/09 This notice includes violations for the areas noted. Routine safety inspection of public and common areas at 140 - 144 albion street / 12 - 16 camp street. chapters 1, 2, & 3 of the san francisco housing code require that the department of building inspection perform periodic health & safety inspections of residential property. this routine inspection was conducted to assure that all requirements have been met per attached routine inspection checklist. Not active
04/15/09 06/05/09 Repair or replace malfunctioning emergency exit lights in public hallways / stairs (504, 1001 hc) Have the emergency lights tested annually and replace any malfunctioning units or expired backup batteries as required. Not active
04/15/09 06/05/09 Provide fire extinguishers type 2a 10bc or equivalent.(905, 1001(n)hc / 3.29 sffc) A minimum of one '2-a:10-b:c' extinguisher for each 3,000 square feet of floor area is required. travel distance shall not exceed 75 feet to the nearest extinguisher. all fire extinguishers are required to be recharged and serviced annually and date tag must be current and posted by a qualified professional vendor. check the pressure gauge periodically as occasionally the seal may leaks and the unit becomes ineffective. Not active
04/15/09 06/05/09 Provide battery operated smoke detector at top of each enclosed stairs (909, 911 hc) A battery operated smoke detector is required at the top of each enclosed stairs / penthouse area and every third floor from the top. test smoke detectors on a regular basis and replace all batteries annually to maintain a working and functional device. Not active
04/15/09 06/05/09 Provide 1/2" throw deadlatch or single cylinder 1" throw deadbolt locks for rear or secondary door (706 hc) At secondary back door - top unit. Not active
04/15/09 06/05/09 This notice includes violations for the areas noted. Routine safety inspection of public and common areas at 140 - 144 albion street / 12 - 16 camp street. chapters 1, 2, & 3 of the san francisco housing code require that the department of building inspection perform periodic health & safety inspections of residential property. this routine inspection was conducted to assure that all requirements have been met per attached routine inspection checklist. Not active
04/15/09 06/05/09 Repair or replace malfunctioning emergency exit lights in public hallways / stairs (504, 1001 hc) Have the emergency lights tested annually and replace any malfunctioning units or expired backup batteries as required. Not active
04/15/09 06/05/09 Provide fire extinguishers type 2a 10bc or equivalent.(905, 1001(n)hc / 3.29 sffc) A minimum of one '2-a:10-b:c' extinguisher for each 3,000 square feet of floor area is required. travel distance shall not exceed 75 feet to the nearest extinguisher. all fire extinguishers are required to be recharged and serviced annually and date tag must be current and posted by a qualified professional vendor. check the pressure gauge periodically as occasionally the seal may leaks and the unit becomes ineffective. Not active
04/15/09 06/05/09 Provide battery operated smoke detector at top of each enclosed stairs (909, 911 hc) A battery operated smoke detector is required at the top of each enclosed stairs / penthouse area and every third floor from the top. test smoke detectors on a regular basis and replace all batteries annually to maintain a working and functional device. Not active
04/15/09 06/05/09 Provide 1/2" throw deadlatch or single cylinder 1" throw deadbolt locks for rear or secondary door (706 hc) At secondary back door - top unit. Not active
04/15/09 06/05/09 This notice includes violations for the areas noted. Routine safety inspection of public and common areas at 140 - 144 albion street / 12 - 16 camp street. chapters 1, 2, & 3 of the san francisco housing code require that the department of building inspection perform periodic health & safety inspections of residential property. this routine inspection was conducted to assure that all requirements have been met per attached routine inspection checklist. Not active
04/15/09 06/05/09 Repair or replace malfunctioning emergency exit lights in public hallways / stairs (504, 1001 hc) Have the emergency lights tested annually and replace any malfunctioning units or expired backup batteries as required. Not active
04/15/09 06/05/09 Provide fire extinguishers type 2a 10bc or equivalent.(905, 1001(n)hc / 3.29 sffc) A minimum of one '2-a:10-b:c' extinguisher for each 3,000 square feet of floor area is required. travel distance shall not exceed 75 feet to the nearest extinguisher. all fire extinguishers are required to be recharged and serviced annually and date tag must be current and posted by a qualified professional vendor. check the pressure gauge periodically as occasionally the seal may leaks and the unit becomes ineffective. Not active
04/15/09 06/05/09 Provide battery operated smoke detector at top of each enclosed stairs (909, 911 hc) A battery operated smoke detector is required at the top of each enclosed stairs / penthouse area and every third floor from the top. test smoke detectors on a regular basis and replace all batteries annually to maintain a working and functional device. Not active
04/15/09 06/05/09 Provide 1/2" throw deadlatch or single cylinder 1" throw deadbolt locks for rear or secondary door (706 hc) At secondary back door - top unit. Not active
04/15/09 06/05/09 This notice includes violations for the areas noted. Routine safety inspection of public and common areas at 140 - 144 albion street / 12 - 16 camp street. chapters 1, 2, & 3 of the san francisco housing code require that the department of building inspection perform periodic health & safety inspections of residential property. this routine inspection was conducted to assure that all requirements have been met per attached routine inspection checklist. Not active
04/15/09 06/05/09 Repair or replace malfunctioning emergency exit lights in public hallways / stairs (504, 1001 hc) Have the emergency lights tested annually and replace any malfunctioning units or expired backup batteries as required. Not active
04/15/09 06/05/09 Provide fire extinguishers type 2a 10bc or equivalent.(905, 1001(n)hc / 3.29 sffc) A minimum of one '2-a:10-b:c' extinguisher for each 3,000 square feet of floor area is required. travel distance shall not exceed 75 feet to the nearest extinguisher. all fire extinguishers are required to be recharged and serviced annually and date tag must be current and posted by a qualified professional vendor. check the pressure gauge periodically as occasionally the seal may leaks and the unit becomes ineffective. Not active
05/17/04 08/18/04 Post enclosed gas meter instructional diagram in a public area. (712 hc) Not active
05/17/04 08/18/04 Repair fire proofing with approved materials (hc 1001(m), 809) Ceiling in basement is damaged and in some areas, plaster is missing. repair/replace with approved fire resistant materials. Not active
05/17/04 08/18/04 Recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc) It has been over one year since last recharge of fire extinguishers in common areas - recharge and date tag all extinguishers. Not active
05/17/04 08/18/04 Inspector comments It is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. Not active
05/17/04 08/18/04 Repair/replace gas heater (1001-f hc) In unit #14, gas space heater does not work and metal cover is not properly attached to the wall. have heating professional service heater and adjust/repair/replace as needed so that heater works properly and heating requirements are met. at reinspection provide housing inspector with documentation that heater was serviced and is in good working condition.note: all required heat sources must be permanently installed. Plumbing permit and/or electrical permit will be required for any changes to the heating systems. Not active
05/17/04 08/18/04 Repair lightswitch (1001e hc) In unit #14, light switch in hallway by kitchen is shorting out. repair /replace light switch. electrical permit is required for any rewiring. Not active
05/17/04 08/18/04 Permanently remove combustible storage or provide automatic fire sprinklers. (904, 1001(i) hc) At time of inspection excessive combustible storage was noted in the basement. remove combustibles from basement such as empty cardboard boxes, stuffed furniture, mattresses, carpet, clothes, loose paper and flammible liquids or provide sprinklers. keep all non-combustible storage neatly boxed and away from exit pathways. Not active
05/17/04 08/18/04 This notice includes violations for the areas noted. All violations listed below are located in unit #14 unless otherwise noted. Not active
05/17/04 08/18/04 Provide smoke enclosure door closer (807 hc) Smoke enclosure door at top of stairway has no door closer. Provide approved door closer and, if necessary, adjust so this smoke enclosure door self closes fully and latches. Not active
05/17/04 08/18/04 Provide shutoff tool for gas utility shutoff (712 hc) At gas meters Not active
05/17/04 08/18/04 Inspector comments It is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. Not active
05/17/04 08/18/04 Repair lightswitch (1001e hc) In unit #14, light switch in hallway by kitchen is shorting out. repair /replace light switch. electrical permit is required for any rewiring. Not active
05/17/04 08/18/04 Post enclosed gas meter instructional diagram in a public area. (712 hc) Not active
05/17/04 08/18/04 Repair fire proofing with approved materials (hc 1001(m), 809) Ceiling in basement is damaged and in some areas, plaster is missing. repair/replace with approved fire resistant materials. Not active
05/17/04 08/18/04 Recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc) It has been over one year since last recharge of fire extinguishers in common areas - recharge and date tag all extinguishers. Not active
05/17/04 08/18/04 Repair/replace gas heater (1001-f hc) In unit #14, gas space heater does not work and metal cover is not properly attached to the wall. have heating professional service heater and adjust/repair/replace as needed so that heater works properly and heating requirements are met. at reinspection provide housing inspector with documentation that heater was serviced and is in good working condition.note: all required heat sources must be permanently installed. Plumbing permit and/or electrical permit will be required for any changes to the heating systems. Not active
05/17/04 08/18/04 Permanently remove combustible storage or provide automatic fire sprinklers. (904, 1001(i) hc) At time of inspection excessive combustible storage was noted in the basement. remove combustibles from basement such as empty cardboard boxes, stuffed furniture, mattresses, carpet, clothes, loose paper and flammible liquids or provide sprinklers. keep all non-combustible storage neatly boxed and away from exit pathways. Not active
05/17/04 08/18/04 This notice includes violations for the areas noted. All violations listed below are located in unit #14 unless otherwise noted. Not active
05/17/04 08/18/04 Provide smoke enclosure door closer (807 hc) Smoke enclosure door at top of stairway has no door closer. Provide approved door closer and, if necessary, adjust so this smoke enclosure door self closes fully and latches. Not active
05/17/04 08/18/04 Provide shutoff tool for gas utility shutoff (712 hc) At gas meters Not active
05/17/04 08/18/04 Post enclosed gas meter instructional diagram in a public area. (712 hc) Not active
05/17/04 08/18/04 Repair fire proofing with approved materials (hc 1001(m), 809) Ceiling in basement is damaged and in some areas, plaster is missing. repair/replace with approved fire resistant materials. Not active
05/17/04 08/18/04 Recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc) It has been over one year since last recharge of fire extinguishers in common areas - recharge and date tag all extinguishers. Not active
05/17/04 08/18/04 Inspector comments It is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. Not active
05/17/04 08/18/04 Repair/replace gas heater (1001-f hc) In unit #14, gas space heater does not work and metal cover is not properly attached to the wall. have heating professional service heater and adjust/repair/replace as needed so that heater works properly and heating requirements are met. at reinspection provide housing inspector with documentation that heater was serviced and is in good working condition.note: all required heat sources must be permanently installed. Plumbing permit and/or electrical permit will be required for any changes to the heating systems. Not active
05/17/04 08/18/04 Repair lightswitch (1001e hc) In unit #14, light switch in hallway by kitchen is shorting out. repair /replace light switch. electrical permit is required for any rewiring. Not active
05/17/04 08/18/04 Permanently remove combustible storage or provide automatic fire sprinklers. (904, 1001(i) hc) At time of inspection excessive combustible storage was noted in the basement. remove combustibles from basement such as empty cardboard boxes, stuffed furniture, mattresses, carpet, clothes, loose paper and flammible liquids or provide sprinklers. keep all non-combustible storage neatly boxed and away from exit pathways. Not active
05/17/04 08/18/04 This notice includes violations for the areas noted. All violations listed below are located in unit #14 unless otherwise noted. Not active
05/17/04 08/18/04 Provide smoke enclosure door closer (807 hc) Smoke enclosure door at top of stairway has no door closer. Provide approved door closer and, if necessary, adjust so this smoke enclosure door self closes fully and latches. Not active
05/17/04 08/18/04 Provide shutoff tool for gas utility shutoff (712 hc) At gas meters Not active
05/17/04 08/18/04 Post enclosed gas meter instructional diagram in a public area. (712 hc) Not active
05/17/04 08/18/04 Post enclosed gas meter instructional diagram in a public area. (712 hc) Not active
05/17/04 08/18/04 Repair fire proofing with approved materials (hc 1001(m), 809) Ceiling in basement is damaged and in some areas, plaster is missing. repair/replace with approved fire resistant materials. Not active
05/17/04 08/18/04 Recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc) It has been over one year since last recharge of fire extinguishers in common areas - recharge and date tag all extinguishers. Not active
05/17/04 08/18/04 Inspector comments It is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. Not active
05/17/04 08/18/04 Repair/replace gas heater (1001-f hc) In unit #14, gas space heater does not work and metal cover is not properly attached to the wall. have heating professional service heater and adjust/repair/replace as needed so that heater works properly and heating requirements are met. at reinspection provide housing inspector with documentation that heater was serviced and is in good working condition.note: all required heat sources must be permanently installed. Plumbing permit and/or electrical permit will be required for any changes to the heating systems. Not active
05/17/04 08/18/04 Repair lightswitch (1001e hc) In unit #14, light switch in hallway by kitchen is shorting out. repair /replace light switch. electrical permit is required for any rewiring. Not active
05/17/04 08/18/04 Permanently remove combustible storage or provide automatic fire sprinklers. (904, 1001(i) hc) At time of inspection excessive combustible storage was noted in the basement. remove combustibles from basement such as empty cardboard boxes, stuffed furniture, mattresses, carpet, clothes, loose paper and flammible liquids or provide sprinklers. keep all non-combustible storage neatly boxed and away from exit pathways. Not active
05/17/04 08/18/04 This notice includes violations for the areas noted. All violations listed below are located in unit #14 unless otherwise noted. Not active
05/17/04 08/18/04 Provide smoke enclosure door closer (807 hc) Smoke enclosure door at top of stairway has no door closer. Provide approved door closer and, if necessary, adjust so this smoke enclosure door self closes fully and latches. Not active
05/17/04 08/18/04 Provide shutoff tool for gas utility shutoff (712 hc) At gas meters Not active
05/17/04 08/18/04 Post enclosed gas meter instructional diagram in a public area. (712 hc) Not active
05/17/04 08/18/04 Repair fire proofing with approved materials (hc 1001(m), 809) Ceiling in basement is damaged and in some areas, plaster is missing. repair/replace with approved fire resistant materials. Not active
05/17/04 08/18/04 Recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc) It has been over one year since last recharge of fire extinguishers in common areas - recharge and date tag all extinguishers. Not active
05/17/04 08/18/04 Inspector comments It is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. Not active
05/17/04 08/18/04 Repair/replace gas heater (1001-f hc) In unit #14, gas space heater does not work and metal cover is not properly attached to the wall. have heating professional service heater and adjust/repair/replace as needed so that heater works properly and heating requirements are met. at reinspection provide housing inspector with documentation that heater was serviced and is in good working condition.note: all required heat sources must be permanently installed. Plumbing permit and/or electrical permit will be required for any changes to the heating systems. Not active
05/17/04 08/18/04 Repair lightswitch (1001e hc) In unit #14, light switch in hallway by kitchen is shorting out. repair /replace light switch. electrical permit is required for any rewiring. Not active
05/17/04 08/18/04 Permanently remove combustible storage or provide automatic fire sprinklers. (904, 1001(i) hc) At time of inspection excessive combustible storage was noted in the basement. remove combustibles from basement such as empty cardboard boxes, stuffed furniture, mattresses, carpet, clothes, loose paper and flammible liquids or provide sprinklers. keep all non-combustible storage neatly boxed and away from exit pathways. Not active
05/17/04 08/18/04 This notice includes violations for the areas noted. All violations listed below are located in unit #14 unless otherwise noted. Not active
05/17/04 08/18/04 Provide smoke enclosure door closer (807 hc) Smoke enclosure door at top of stairway has no door closer. Provide approved door closer and, if necessary, adjust so this smoke enclosure door self closes fully and latches. Not active
05/17/04 08/18/04 Provide shutoff tool for gas utility shutoff (712 hc) At gas meters Not active
05/17/04 08/18/04 Repair fire proofing with approved materials (hc 1001(m), 809) Ceiling in basement is damaged and in some areas, plaster is missing. repair/replace with approved fire resistant materials. Not active
05/17/04 08/18/04 Recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc) It has been over one year since last recharge of fire extinguishers in common areas - recharge and date tag all extinguishers. Not active
05/17/04 08/18/04 Inspector comments It is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. Not active
05/17/04 08/18/04 Repair/replace gas heater (1001-f hc) In unit #14, gas space heater does not work and metal cover is not properly attached to the wall. have heating professional service heater and adjust/repair/replace as needed so that heater works properly and heating requirements are met. at reinspection provide housing inspector with documentation that heater was serviced and is in good working condition.note: all required heat sources must be permanently installed. Plumbing permit and/or electrical permit will be required for any changes to the heating systems. Not active
05/17/04 08/18/04 Repair lightswitch (1001e hc) In unit #14, light switch in hallway by kitchen is shorting out. repair /replace light switch. electrical permit is required for any rewiring. Not active
05/17/04 08/18/04 Permanently remove combustible storage or provide automatic fire sprinklers. (904, 1001(i) hc) At time of inspection excessive combustible storage was noted in the basement. remove combustibles from basement such as empty cardboard boxes, stuffed furniture, mattresses, carpet, clothes, loose paper and flammible liquids or provide sprinklers. keep all non-combustible storage neatly boxed and away from exit pathways. Not active
05/17/04 08/18/04 This notice includes violations for the areas noted. All violations listed below are located in unit #14 unless otherwise noted. Not active
05/17/04 08/18/04 Provide smoke enclosure door closer (807 hc) Smoke enclosure door at top of stairway has no door closer. Provide approved door closer and, if necessary, adjust so this smoke enclosure door self closes fully and latches. Not active
05/17/04 08/18/04 Provide shutoff tool for gas utility shutoff (712 hc) At gas meters Not active

Building Complaints (4 found)

Complaint Number Date Filed Date Abated Division Description Status
201252245 07/30/12 Housing Inspection Services The front of the building was scraped/sanded and painted. they have finished the work, but have left a lot of paint chips all over the sidewalk and in the dirt around the trees. Not Active
200902041 04/15/09 06/05/09 Housing Inspection Services Routine safety inspection Not Active
200450143 05/17/04 08/18/04 Housing Inspection Services No heat -complainanthas a wall furnace. Not Active
200342004 07/10/03 11/25/08 Housing Inspection Services Routines Not Active

Owner Portfolio (1 found)

Address Units Class
0144 0140 Albion St 6 Apartment 5 to 14 Units

311 Calls (DPH & DBI only) (0 found)

Health Inspections (food service) (0 found)

Health Inspections (apartments) - data coming soon!

Soft Story Retrofit Program (2 found)

Tier Status
4 Work Complete, CFC Issued

Section 604 Affidavit (0 found)

Planning Records (0 found)

Building Permits (9 found)

Permit Number Creation Date Cost Description Status
M1212268 06/19/20 $ Street space Issued
M1040407 02/15/19 $ Street space Issued
M1040407 02/15/19 $ Street space Issued
201807134558 07/13/18 $45000 Mandatory seismic soft story retrofit per sfebc chapber 4d: 2016 cebc appendix a-4, ab-107 Complete
201807134558 07/13/18 $45000 Mandatory seismic soft story retrofit per sfebc chapber 4d: 2016 cebc appendix a-4, ab-107 Complete
M23479 04/21/03 $ Sidewalk permit Issued
M23479 04/21/03 $ Sidewalk permit Issued
200112044414 12/04/01 $6450 Reroofing Complete
8905952 04/12/89 $4000 Reroofing Complete

Electrical Permits (2 found)

Permit Number Creation Date Description Status
E200803035829 03/03/08 12 lights, 8 switches, 20 receptacles, 10 circuits & 1 panel/switchboard - rewire entire unit. Complete
E200407074858 07/07/04 Repair one edfective switch Complete

Plumbing Permits (1 found)

Permit Number Creation Date Type Status
PW20200108230 01/08/20 Complete

Fire Violations (0 found)

Fire Complaints (0 found)

Fire Incidents (0 found)

Fire Inspections (0 found)

Buyouts (2 found)

Address Date Agreed Date Disclosed Amount Number of Tenants
136 Albion Street 10/19/15 $
139 Albion Street 05/05/16 $


About Augrented

Augrented uses public data on apartments and landlords from the San Francisco & New York City Open Data portals and other official sources, to provide apartment and landlord ratings. Access is provided in accordance with California and/or New York State law and SF & NYC agency policies, local laws and ordinances. This service is not provided or endorsed by the DBI, HPD or any other city or government agency.